3 | 1 | Laurent GUERBY | h1. Onduleur |
4 | 1 | Laurent GUERBY | |
5 | 1 | Laurent GUERBY | h2. PowerWalker VI 650 LCD |
6 | 1 | Laurent GUERBY | |
7 | 1 | Laurent GUERBY | http://www.powerwalker.com/line-interactive.asp?VA_level=650 |
8 | 1 | Laurent GUERBY | Modèle 650 VA 360W 12V 7Ah 4.3 kg |
9 | 1 | Laurent GUERBY | Modèle 850 VA 480W 12V 9Ah 5kg aussi disponible |
10 | 1 | Laurent GUERBY | |
11 | 1 | Laurent GUERBY | - USB data |
12 | 1 | Laurent GUERBY | - 2 prises schuko et filtre RJ11 |
13 | 1 | Laurent GUERBY | |
14 | 1 | Laurent GUERBY | Entre 50 et 60 euros |
15 | 1 | Laurent GUERBY | * http://www.priceminister.com/offer?action=desc&aid=526668530 |
16 | 1 | Laurent GUERBY | |
17 | 1 | Laurent GUERBY | Supporté sous debian squeeze par défaut : |
18 | 1 | Laurent GUERBY | |
19 | 1 | Laurent GUERBY | <pre> |
20 | 1 | Laurent GUERBY | apt-get install nut |
21 | 1 | Laurent GUERBY | # edit /etc/nut/upsd.users to add |
22 | 1 | Laurent GUERBY | [admin] |
23 | 1 | Laurent GUERBY | password = mypass |
24 | 1 | Laurent GUERBY | actions = SET |
25 | 1 | Laurent GUERBY | instcmds = ALL |
26 | 1 | Laurent GUERBY | # edit /etc/nut/nut.conf to add |
27 | 1 | Laurent GUERBY | MODE=standalone |
28 | 1 | Laurent GUERBY | # edit /etc/nut/ups.conf to add |
29 | 1 | Laurent GUERBY | [pw] |
30 | 1 | Laurent GUERBY | driver = blazer_usb |
31 | 1 | Laurent GUERBY | port = /dev/hidraw0 |
32 | 1 | Laurent GUERBY | vendorid = 0665 |
33 | 1 | Laurent GUERBY | productid = 5161 |
34 | 1 | Laurent GUERBY | # Then |
35 | 1 | Laurent GUERBY | /etc/init.d/nut restart |
36 | 1 | Laurent GUERBY | </pre> |
37 | 1 | Laurent GUERBY | |
38 | 1 | Laurent GUERBY | Commandes : |
39 | 1 | Laurent GUERBY | |
40 | 1 | Laurent GUERBY | <pre> |
41 | 1 | Laurent GUERBY | # upsc -l |
42 | 1 | Laurent GUERBY | pw |
43 | 1 | Laurent GUERBY | # upsc pw |
44 | 1 | Laurent GUERBY | battery.voltage: 13.50 |
45 | 1 | Laurent GUERBY | battery.voltage.nominal: 12.0 |
46 | 1 | Laurent GUERBY | beeper.status: enabled |
47 | 1 | Laurent GUERBY | device.type: ups |
48 | 1 | Laurent GUERBY | driver.name: blazer_usb |
49 | 1 | Laurent GUERBY | driver.parameter.pollinterval: 2 |
50 | 1 | Laurent GUERBY | driver.parameter.port: /dev/hidraw0 |
51 | 1 | Laurent GUERBY | driver.parameter.productid: 5161 |
52 | 1 | Laurent GUERBY | driver.parameter.vendorid: 0665 |
53 | 1 | Laurent GUERBY | driver.version: 2.4.3 |
54 | 1 | Laurent GUERBY | driver.version.internal: 0.03 |
55 | 1 | Laurent GUERBY | input.current.nominal: 2.0 |
56 | 1 | Laurent GUERBY | input.frequency: 50.0 |
57 | 1 | Laurent GUERBY | input.frequency.nominal: 50 |
58 | 1 | Laurent GUERBY | input.voltage: 231.5 |
59 | 1 | Laurent GUERBY | input.voltage.fault: 231.5 |
60 | 1 | Laurent GUERBY | input.voltage.nominal: 230 |
61 | 1 | Laurent GUERBY | output.voltage: 231.5 |
62 | 1 | Laurent GUERBY | ups.delay.shutdown: 30 |
63 | 1 | Laurent GUERBY | ups.delay.start: 180 |
64 | 1 | Laurent GUERBY | ups.load: 2 |
65 | 1 | Laurent GUERBY | ups.productid: 5161 |
66 | 1 | Laurent GUERBY | ups.status: OL |
67 | 1 | Laurent GUERBY | ups.type: offline / line interactive |
68 | 1 | Laurent GUERBY | ups.vendorid: 0665 |
69 | 1 | Laurent GUERBY | # upscmd -u admin -p mypass -l pw |
70 | 1 | Laurent GUERBY | Instant commands supported on UPS [pw]: |
71 | 1 | Laurent GUERBY | |
72 | 1 | Laurent GUERBY | beeper.toggle - Toggle the UPS beeper |
73 | 1 | Laurent GUERBY | load.off - Turn off the load immediately |
74 | 1 | Laurent GUERBY | load.on - Turn on the load immediately |
75 | 1 | Laurent GUERBY | shutdown.return - Turn off the load and return when power is back |
76 | 1 | Laurent GUERBY | shutdown.stayoff - Turn off the load and remain off |
77 | 1 | Laurent GUERBY | shutdown.stop - Stop a shutdown in progress |
78 | 1 | Laurent GUERBY | test.battery.start - Start a battery test |
79 | 1 | Laurent GUERBY | test.battery.start.deep - Start a deep battery test |
80 | 1 | Laurent GUERBY | test.battery.start.quick - Start a quick battery test |
81 | 1 | Laurent GUERBY | test.battery.stop - Stop the battery test |
82 | 1 | Laurent GUERBY | # upscmd -u admin -p mypass pw beeper.toggle |
83 | 1 | Laurent GUERBY | # upscmd -u admin -p mypass pw shutdown.return |
84 | 1 | Laurent GUERBY | # upscmd -u admin -p mypass pw load.off |
85 | 1 | Laurent GUERBY | # upscmd -u admin -p mypass pw load.on |
86 | 1 | Laurent GUERBY | # upscmd -u admin -p mypass pw test.battery.start.quick |
87 | 1 | Laurent GUERBY | </pre> |
88 | 1 | Laurent GUERBY | |
89 | 1 | Laurent GUERBY | La commande shutdown.return coupe la charge pendant 3 minutes environ et donc permet un reboot a distance des equipements sur l'onduleur. |
90 | 1 | Laurent GUERBY | |
91 | 1 | Laurent GUERBY | Quand l'electricité n'est plus disponible ups.status pas a "OB" et battery.voltage decroit par palier de 0.1V. ups.load donne la charge approximative en %. |
92 | 1 | Laurent GUERBY | |
93 | 1 | Laurent GUERBY | L'onduleur revient bien en ligne si on épuise les batteries mais qu'on remet le courant. |
94 | 1 | Laurent GUERBY | |
95 | 1 | Laurent GUERBY | Tiens plus d'une heure sur une charge de 20 Watt. |
96 | 1 | Laurent GUERBY | |
97 | 2 | Laurent GUERBY | h2. DC-DC |
98 | 2 | Laurent GUERBY | |
99 | 2 | Laurent GUERBY | Avec controle USB via obinou : http://www.mini-box.com/DCDC-USB |
100 | 2 | Laurent GUERBY | |
101 | 1 | Laurent GUERBY | h2. Autre |