Onduleur¶
PowerWalker VI 650 LCD¶
http://www.powerwalker.com/line-interactive.asp?VA_level=650
Modèle 650 VA 360W 12V 7Ah 4.3 kg
Modèle 850 VA 480W 12V 9Ah 5kg aussi disponible
- USB data
- 2 prises schuko et filtre RJ11
Supporté sous debian squeeze par défaut :
apt-get install nut # edit /etc/nut/upsd.users to add [admin] password = mypass actions = SET instcmds = ALL # edit /etc/nut/nut.conf to add MODE=standalone # edit /etc/nut/ups.conf to add [pw] driver = blazer_usb port = /dev/hidraw0 vendorid = 0665 productid = 5161 # Then /etc/init.d/nut restart
Commandes :
# upsc -l pw # upsc pw battery.voltage: 13.50 battery.voltage.nominal: 12.0 beeper.status: enabled device.type: ups driver.name: blazer_usb driver.parameter.pollinterval: 2 driver.parameter.port: /dev/hidraw0 driver.parameter.productid: 5161 driver.parameter.vendorid: 0665 driver.version: 2.4.3 driver.version.internal: 0.03 input.current.nominal: 2.0 input.frequency: 50.0 input.frequency.nominal: 50 input.voltage: 231.5 input.voltage.fault: 231.5 input.voltage.nominal: 230 output.voltage: 231.5 ups.delay.shutdown: 30 ups.delay.start: 180 ups.load: 2 ups.productid: 5161 ups.status: OL ups.type: offline / line interactive ups.vendorid: 0665 # upscmd -u admin -p mypass -l pw Instant commands supported on UPS [pw]: beeper.toggle - Toggle the UPS beeper load.off - Turn off the load immediately load.on - Turn on the load immediately shutdown.return - Turn off the load and return when power is back shutdown.stayoff - Turn off the load and remain off shutdown.stop - Stop a shutdown in progress test.battery.start - Start a battery test test.battery.start.deep - Start a deep battery test test.battery.start.quick - Start a quick battery test test.battery.stop - Stop the battery test # upscmd -u admin -p mypass pw beeper.toggle # upscmd -u admin -p mypass pw shutdown.return # upscmd -u admin -p mypass pw load.off # upscmd -u admin -p mypass pw load.on # upscmd -u admin -p mypass pw test.battery.start.quick
La commande shutdown.return coupe la charge pendant 3 minutes environ et donc permet un reboot a distance des equipements sur l'onduleur.
Quand l'electricité n'est plus disponible ups.status pas a "OB" et battery.voltage decroit par palier de 0.1V. ups.load donne la charge approximative en %.
L'onduleur revient bien en ligne si on épuise les batteries mais qu'on remet le courant.
Tiens plus d'une heure sur une charge de 20 Watt.
DC-DC¶
Avec controle USB via obinou : http://www.mini-box.com/DCDC-USB
http://www.cartft.com/catalog/il/1114
Autre¶
TODO